ChevronGaviota-1
Gas Turbine Generator Package Designed by MTSI. Custom engineered pulse clean air filter package with divided plenum for combustion & generator air. Generator compartment positively pressurized. Turbine compartment negatively pressurized by redundant exhaust fans. Generator cooling air discharges from screened hood on top of main air cleaner package.
ChevronGaviota-2
View showing heat recovery steam generators each rated at 72,000 pph, 100psig. Diverter valves and boiler outlets are manifolded through reheat duct burner, SCR and secondary HRSG. Boilers contain two LP evaporator sections with duct burner between the two evaporators. (1 of 2)
ChevronGaviota-3
View showing heat recovery steam generators each rated at 72,000 pph, 100psig. Diverter valves and boiler outlets are manifolded through reheat duct burner, SCR and secondary HRSG. Boilers contain two LP evaporator sections with duct burner between the two evaporators. (2 of 2)
ChevronGaviota-4
Gas Turbine Generator Unit Control Panels with bus tie panel designed and manufactured by MTSI. Unit Control Panels included Woodward electronic fuel and water/fuel ratio controllers, Gould Programmable Logic Controllers and Bently Nevada Vibration & Temperature Monitors.